Incinerators to be suitable for the professional disposal of clinical & medical waste / garbage with a higher load capacity in the range of approximately
1000-1500 Kg. The durable, self-contained incinerators shall offer an effective and highly efficient, safe disposal and to be manufactured according to applicable international directives, e.g. CE, EU, etc.
Type of Fuel: Diesel or Petrol or Natural Gas. Temperature controlled,
efficient burner for optimum fuel economy. incinerator in the best technology and an approximate capacity of 2000 ton / year. Possibly an incineration capacity of 200 kg / hr and a calorific value of 7500 kcal / kg. Industrial and domestical waste.INCINERATOR For incineration of Laboratory wastes materials
Features
i.Smoke and smell free
ii.High Temperature , refractory lining with excellent heat retention
iii.Quick heat up time
iv.Must have a secondary chamber
v.Constant run fan
vi.Temperature monitoring
vii.Thermostat Control
Technical Specifications
i.Capacity : approx. 0.20 m3
ii.Fuel consumption: 5 litres /hour Diesel Oil
iii.Min Operating Temp: 900 oC
iv.Max Operating Temp: 1350 oC
v.Residence Time: 2 sec
vi.Burning rate: 35kg/hr minimum
Accessories
Standard accessories required
Consumables and Spares
Supplied with spares and consumables to carry out at least 1000 tests